Navien · Boiler troubleshooting
Connect the NFB-301C/399C boiler to the gateway R1 port
What is going on
The R1 port takes the boiler RS-485 link through a 3-pin Phoenix connector that plugs into the boiler terminal block on the right side of the front panel. Use standard RS-485 grounding.
Check in this order
- Make sure R1 DIP switch 4 is OFF.
- Connect the gateway R1 3-pin Phoenix connector to the 3-pin terminal block on the boiler front panel.
- Match the pins gateway A (TX+) to boiler +, gateway B (RX-) to boiler -, gateway G (GND) to boiler GND.
- Use standard grounding practice for the RS-485 GND.
Applies to: NFB-301C and NFB-399C boilers connected to gateway R1
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Modbus/BACnet Gateway Start-up Guide, p. 8. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.