Refit burner and check all gas equipment for leaks
What is going on
Final check after burner refit. Only use approved leak detection products and remove residue afterward.
Check in this order
- Insert the burner and tighten the four nuts evenly and crosswise to 3 lb.ft (4 Nm).
- Fit the gas supply pipe with a new gasket and tighten to 11 lb.ft (15 Nm).
- Plug in the ventilation air intake adaptor.
- Reconnect the electrical leads.
- Check all gas equipment for tightness at operating pressure with an approved leak detection agent.
- Do not use leak detectors containing nitrites or sulphides. Remove all residue after testing.
Applies to: Vitocrossal 300 CU3A 26 to 199
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocrossal 300 CU3A 26 to 199 Service Instructions, p. 27. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.