Viessmann · Boiler troubleshooting

Check rotational direction of mixing valve motor (extension kit)

Vitodens 200-W B2HA

What is going on

The boiler runs a self-test at power-up, during which the mixing valve opens and closes. If the flow temperature drops when the valve is opened, the motor turns the wrong way or the valve set is fitted incorrectly.

Likely causes

  • Mixing valve motor turning the wrong direction
  • Mixing valve set incorrectly fitted

Check in this order

  1. After power-up, let the self-test run.
  2. Set the mixing valve manually to Open.
  3. Check that the flow temperature sensor reads a higher temperature.
  4. If the temperature drops, remove the upper casing cover of the extension kit.
  5. At plug gS, swap the cores at terminals | and ~.
  6. Refit the casing cover.

Applies to: Extension kit with mixing valve, heating circuit 2 or 3

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitodens 200-W B2HA 19, 28, 35 Service Instructions, p. 81. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.