Weil-McLain · Boiler troubleshooting
Multiple boiler terminations and vent/air clearances
What is going on
Spacing rules when more than one SlimFit boiler terminates on the same wall or roof.
Likely causes
- Vent outlets and air inlets at different heights
- Vent pipe of one boiler too close to the air inlet of the next
Check in this order
- Terminate every vent/air connection as described in this manual for individual vents.
- Set all vent pipes and air inlets at the same height.
- Place wall penetrations for at least 12 in between a vent pipe and the adjacent air inlet elbow (US installations).
- For Canadian installations, follow the clearances in CSA B149.1 or B149.2.
- Treat the direct vent air inlet as part of a direct vent connection, not as a forced air intake for spacing from adjacent vents.
- Space terminations for good installation practice and required maintenance access.
Applies to: SF-550 and SF-750 with multiple boilers
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: SlimFit series 3 commercial gas-fired water boiler manual, p. 33 and p. 40. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.