Viessmann · Boiler troubleshooting
Lighting and operating instructions (gas boiler)
What is going on
Boiler has no pilot; the ignition device lights the burner automatically. Never try to light the burner by hand. Before operating, smell around the boiler, including near the floor, for gas. If gas is smelled, do not operate any switch or phone in the building, leave and call the gas supplier from outside, or the fire department if the supplier cannot be reached. Only use hand force on the main gas supply switch.
Check in this order
- Set the thermostat or control to lowest setting.
- Turn off all electric power to the boiler.
- Close the main gas shut-off valve.
- Wait five minutes to clear any gas, then smell for gas including near the floor.
- If no gas is smelled, open the main gas shut-off valve.
- Turn on electric power to the boiler.
- Set the thermostat or control to the desired setting.
- If the boiler will not operate, turn off gas to the boiler and call the service technician or gas supplier.
Applies to: B1HE and B1KE Combi boilers, natural gas or LPG
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitodens 100-W B1HE/B1KE Combi installation/service manual, p. 125. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.