Field test of fixed high limit, simulation 3 (CSD-1)
What is going on
Tests the control's response to a limit switch wiring fault. This produces a fault that needs manual reset.
Check in this order
- Disconnect one of the wires on the limit switch.
- Confirm the control shows a fault that requires manual reset.
- Reconnect the wire and reset the control manually.
Applies to: Vitodens 222-F, B2TB 19, 35, 68, 125
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitodens 222-F, B2TB installation instructions, p. 7. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.