Viessmann · Boiler troubleshooting

Field test of fixed high limit, simulation 3 (CSD-1)

Vitodens 222-FB2TB

What is going on

Tests the control's response to a limit switch wiring fault. This produces a fault that needs manual reset.

Check in this order

  1. Disconnect one of the wires on the limit switch.
  2. Confirm the control shows a fault that requires manual reset.
  3. Reconnect the wire and reset the control manually.

Applies to: Vitodens 222-F, B2TB 19, 35, 68, 125

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitodens 222-F, B2TB installation instructions, p. 7. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.