Viessmann · Boiler troubleshooting

Control unit power supply connection

Vitotronic 100 GC1Vitotronic 300-K MW1S

What is going on

Power input to the control unit. The control must be grounded and the line, neutral and ground must not be swapped.

Check in this order

  1. Make sure the main supply to the control has overcurrent protection rated at most 15 A and a 2-pole disconnect.
  2. Confirm the line, neutral and ground conductors are not interchanged.
  3. Connect the power supply wire to terminals 11, N and G on the DIN rail in the connection enclosure.
  4. Ground the control.

Applies to: Vitotronic 100 GC1, 120 VAC 1-phase

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotronic 100 GC1 / Vitotronic 300-K MW1S installation and service instructions, p. 53. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.