Viessmann · Boiler troubleshooting

Boiler pump runs continuously after changing to multi-boiler operation

Vitodens 200-W B2HA

What is going on

When switched from single boiler to multi-boiler operation, coding address 30:0 may reset to 30:3, causing the boiler pump to run continuously.

Likely causes

  • Coding address 30 reset to 30:3 during change to multi-boiler operation

Check in this order

  1. Verify the coding address for each boiler is 30:0.
  2. Adjust to 30:0 if necessary.
  3. Refer to page 60 for coding.

Applies to: Multi-boiler operation

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitodens 200-W B2HA 112, 150, 399, 530 service instructions, p. 85. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.