Viessmann · Boiler troubleshooting

Open the burner and combustion chamber on CI2 1500 and 2000

Vitocrossal 200 CI2

What is going on

Work on the burner only after the gas is shut off and the burner has cooled.

Check in this order

  1. Turn the power switch off and disconnect the boiler power supply.
  2. Close the gas shut-off valve.
  3. Flip open the panel handle at the top of the upper front panel.
  4. Pull the upper front panel up by the handle.
  5. While holding the handle, release the retaining clip with a screwdriver and lift the panel off. Keep a firm grip to prevent the panel falling.
  6. Press down the lower front panel release with a screwdriver.
  7. Pull the top of the lower front panel away from the boiler and lift it off.
  8. Let the burner cool before working on it.

Applies to: Vitocrossal 200 CI2 1500, 2000

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocrossal 200 CI2 service instructions, p. 21. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.