Weil-McLain · Boiler troubleshooting

Adjust gas valve throttle screw to correct combustion

Ultra Series 4

What is going on

Only for a qualified technician using calibrated combustion test instruments. Do not adjust the throttle screw at low fire; only check low fire values.

Likely causes

  • Difficulty igniting
  • Poor flame stability at low fire
  • Combustion noise
  • High CO values
  • CO2 outside Figure 42 range at high fire

Check in this order

  1. Set Manual test mode to MAX (high fire) and let the boiler stabilize, then read CO2.
  2. If CO2 is high, turn the throttle screw clockwise to lower input. Let it stabilize and read again. Repeat until the target is reached.
  3. If CO2 is low, turn the throttle screw counterclockwise to raise input. Let it stabilize and read again. Repeat until the target is reached.
  4. Lock the boiler at low fire and check readings. If acceptable, verify high fire again.
  5. Return firing rate to AUTO.
  6. If acceptable values cannot be reached for both high and low fire, contact the WM Technologies representative.

Applies to: Models 80/105 (Figure 39), 155/230/299 (Figure 40), 399 (Figure 41)

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Ultra Series 4 gas-fired water boiler manual, p. 41. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.