Weil-McLain · Boiler troubleshooting

Gas valve offset adjustment at low fire

SlimFit Series 2

What is going on

Set low fire after high fire is correct. Use this only when the low fire combustion readings are outside the acceptable range and throttle screw adjustment does not fix it.

Likely causes

  • Low fire CO2 outside range
  • Unstable low fire flame

Check in this order

  1. Lock the boiler to low fire from the control screen and confirm the low fire RPM matches the blower speed table.
  2. Check combustion readings at low fire.
  3. If acceptable, recheck high fire and return the rate to AUTO.
  4. If not acceptable, remove the cover screw over the offset adjustment.
  5. Use a T40 Torx driver. Turn clockwise to raise CO2, counterclockwise to lower it.
  6. Reinstall the cover screw.
  7. If acceptable readings cannot be reached at both fires, consult the local Weil-McLain representative.

Applies to: SlimFit Series 2 gas valve

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: SlimFit Series 2 boiler manual 550-100-561/1225, p. 82-83. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.