Weil-McLain · Boiler troubleshooting
Boiler does not start correctly
What is going on
Check these items first if the boiler fails to start.
Likely causes
- Loose connection or blown fuse
- Service switch off
- External limit control open
- Boiler water above 200°F
- Closure switch contacts open
- Thermostats set below room temperature
- Gas not on at meter or boiler
- Incoming gas pressure below the minimum on page 24
- Incorrect control settings
- Warm weather shutdown active
Check in this order
- Check for loose connections, a blown fuse or service switch off.
- Check whether external limit controls, if used, are open.
- Confirm boiler water is below 200°F.
- Confirm the closure switch contacts are open.
- Confirm thermostats are set above room temperature.
- Confirm gas is on at the meter and at the boiler.
- Confirm incoming gas pressure meets the minimum on page 24.
- Confirm control settings suit the application and warm weather shutdown is not active.
- If the problem remains, go to the Troubleshooting section starting on page 159.
Applies to: ECO Tec Series 3 80/110/150/199
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: ECO Tec Series 3 Condensing Gas Boiler Boiler Manual, p. 133. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.