Boiler does not start correctly

ECO Tec Series 3

What is going on

Check these items first if the boiler fails to start.

Likely causes

  • Loose connection or blown fuse
  • Service switch off
  • External limit control open
  • Boiler water above 200°F
  • Closure switch contacts open
  • Thermostats set below room temperature
  • Gas not on at meter or boiler
  • Incoming gas pressure below the minimum on page 24
  • Incorrect control settings
  • Warm weather shutdown active

Check in this order

  1. Check for loose connections, a blown fuse or service switch off.
  2. Check whether external limit controls, if used, are open.
  3. Confirm boiler water is below 200°F.
  4. Confirm the closure switch contacts are open.
  5. Confirm thermostats are set above room temperature.
  6. Confirm gas is on at the meter and at the boiler.
  7. Confirm incoming gas pressure meets the minimum on page 24.
  8. Confirm control settings suit the application and warm weather shutdown is not active.
  9. If the problem remains, go to the Troubleshooting section starting on page 159.

Applies to: ECO Tec Series 3 80/110/150/199

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: ECO Tec Series 3 Condensing Gas Boiler Boiler Manual, p. 133. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.