SVF will not start, locks out after 5 minutes waiting on interlock
What is going on
Before firing, the SVF waits for its start interlocks (combustion air damper end switch, boiler valve end switch) to close. If an interlock does not prove within the allowed time (5 minutes by default), the boiler locks out.
Likely causes
- Combustion air damper not opening, or its end switch not closing
- Boiler isolation valve not opening, or its end switch not wired / adjusted
- End switch wired to the wrong input
- Valve slower than the allowed time
Check in this order
- Power off before checking wiring.
- Check which Start Interlock input the end switch is wired to (Start Interlock 1 or 2) and that the input is renamed to match.
- Watch the damper or valve on a call. Make sure it opens fully and the end switch actually closes.
- Check the relay that drives the valve/damper (Relay A to D) is set to the right function.
- If the valve is just slow, raise Start Time Allowed Before Lockout (Settings > All Parameters > Boiler Settings > General Boiler Settings).
- For a bypass valve end switch on Aux 1/2 set it in Cascade Master > Valve Control, and set the time allowed to make the end switch to the valve's closing time.
Applies to: SVF 725, 850, 1000 (Series 1) and SVF 1500-3000 (Series 2)
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Weil-McLain SVF 725/850, 1000 Series 1 / 1500-3000 Series 2 Advanced Installation Manual 550-143-071/0924, Express Setup examples, p.36-37; combustion air damper p.5. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.