Viessmann · Boiler troubleshooting

Making space for accessory adaptors on the DIN rail (CM2 only)

Vitotronic 100 GC1

What is going on

Remove the four spare DIN terminals to free rail space for accessory adaptors.

Check in this order

  1. Push up on the bottom front of the DIN rail clamp to remove it and set it aside.
  2. With a flat-head screwdriver, remove spare DIN terminals 23, 24, 25 and 26 one at a time. Place the screwdriver between the rail and the base of the terminal and turn it clockwise.
  3. Discard the removed terminals.
  4. Reinstall the DIN rail clamp by hooking the latch over the top of the rail, then push down on the front of the clamp.

Applies to: CM2 only

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Viessmann Vitotronic 100 GC1 / Vitocontrol-S VD2/CT3/CM2 installation and service instructions, p. 49. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.