Heating system design version 6: heating circuit plus one low temperature heating circuit
What is going on
Vitocrossal 300 CT3 boilers with Vitotronic 100 GC1, controlled by Vitocontrol-S VD2/CT3/CM2 with outdoor reset, modulating boiler water temperature and load-dependent sequential control. Two-stage or modulating burners are controlled. The boiler has two return connections: higher return temperature circuits go to the upper connection, lower return temperature circuits to the lower connection. Boiler supply temperature is set automatically over LON BUS from the highest required mixing valve circuit temperature plus an adjustable differential.
Check in this order
- Set the coding for system version 6 on every Vitotronic 100 GC1.
- Set the Vitocontrol-S coding as listed in the system version 6 coding table.
- Connect at least 15% of the rated output to the lower return connection.
- Check the connection diagram on site for completeness and function. Single-phase and three-phase pumps need field-supplied motor contactors or starters.
Applies to: Heating system design version 6
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitotronic 100 GC1 / Vitocontrol-S VD2/CT3/CM2 installation and service instructions, p. 19-21. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.