Keeping lead boiler section valves open
What is going on
When the burners are off and all boiler section valves are closed, system venting is no longer guaranteed. The lead boiler's section valves can be held open by an external request.
Check in this order
- Insert an EA1 extension with a fixed jumper at input DE1.
- Send a request from the building management system at the 0-10 V input, for example 2 V (68°F / 20°C).
- Alternatively, send a floating contact request to plug aVH (terminals 2-3).
- Set master coding 5D to 2 and 9B to 1.
Applies to: Lead boiler section valves
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0 installation instructions, p. 33. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.