Wire room thermostats, aquastats and zone valves
What is going on
Inputs are dry contacts only. Supplying 24 V to the thermostat circuits can damage the control.
Check in this order
- Do not supply 24 VDC or 24 VAC power to the thermostat or input circuits.
- Wire Input 1 to P11 terminals 4 and 5, Input 2 to P15 terminals 1 and 2, and Input 3 to P15 terminals 3 and 4.
- If a thermostat needs continuous 24 V, connect its common wire to P11 pin 2 and keep total draw within limits.
- For 3-wire zone valves, use relays to provide dry contacts to the control inputs.
Applies to: Inputs 1, 2 and 3 and their terminal strips
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: SlimFit Series 2 boiler manual 550-100-561/1225, p. 53. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.