Viessmann · Boiler troubleshooting

Return valve protection with low-loss header (Circuit Diagram 8)

Vitotronic 100, GC1

What is going on

When return temperature falls below the minimum, the return valve on the boilers closes proportionally via sensor T1 to protect the boiler.

Likely causes

  • Return temperature below required minimum

Check in this order

  1. Verify sensor T1 is connected at plug aJA and coding 4A is set to 4A: 1.
  2. Verify continuous return temperature control is set (0C: 1).
  3. Size each boiler circuit pump so its supply is at least equal to the maximum possible total heating circuit supply; recommendation is 110%.

Applies to: Circuit Diagram 8, multi-boiler system with low-loss header

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Viessmann Vitotronic 100 GC1 installation and service instructions, p. 22. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.