Glow Brand · Boiler troubleshooting
Removing an existing boiler from a common venting system
What is going on
Use this procedure for each boiler that stays on a common vent after another boiler is removed. The remaining venting is usually too large and must be resized.
Check in this order
- Shut down all boilers on the common venting system before starting.
- Seal any unused openings in the common vent.
- Check the venting for correct size, horizontal pitch, blockage, restriction, leakage, corrosion and other faults.
- Close building doors and windows. Run clothes dryers, exhaust fans and other non-vented appliances. Set exhaust fans to maximum. Close fireplace dampers.
- Start the remaining appliance and run it continuously.
- Test for spillage at the draft hood relief opening after 5 minutes of main burner operation using a match, candle or smoke.
- If the appliance vents correctly, restore doors, windows, fans, dampers and other appliances to normal use.
- Correct any improper operation and resize the common vent to approach the minimum size in the National Fuel Gas Code tables (Chapter 13) or CAN/CSA B149.1.
Applies to: Remaining appliances on a common vent
More boiler guides
Related
Glow Brand error codes · Glow Brand parts · Glow Brand tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Glow Brand C95 & C140 installation & operating manual, p. 18. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.