Weil-McLain · Boiler troubleshooting

Freeze protection operation

SVF Series 1

What is going on

With freeze protection enabled, the control fires the boiler at low fire and starts the selected circulators when heat exchanger sensors read below 45 °F. The burner starts if temperature falls below 40 °F. Circulators and burner stop when temperature rises above 48 °F.

Check in this order

  1. Enable FREEZE PROTECT CIRCS in the BOILER SETTINGS menu.
  2. Choose which circulators should run during freeze protection.
  3. Confirm the heat exchanger sensors read correctly in DIAGNOSTICS > TEMPERATURES.

Applies to: SVF Series 1, single boiler in Basic mode

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: SVF Series 1 boiler manual, p. 75. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.