Weil-McLain · Boiler troubleshooting

Hydrostatic pressure test procedure

Ultra Series 4

What is going on

Pressure test the boiler before connecting permanent piping. Use Figure 2 for the connection layout.

Check in this order

  1. Remove the supply line tees and 3/4 in elbow from the accessory bag and pipe them to the supply connection. Use pipe dope sparingly.
  2. Temporarily plug the 3/4 in relief valve tapping in the street elbow with a 3/4 in NPT plug.
  3. Connect a hose from the fresh water supply to the boiler drain valve. Make sure it can also drain the boiler after the test.
  4. Install a nipple and shutoff valve on the supply tee to bleed air during fill (not included with boiler).
  5. Install a shutoff valve on the return connection (not included with boiler).
  6. Pipe street elbows on top of the shutoff valves and place catch buckets below if you want to avoid water on the boiler.
  7. Open the shutoff valves, then slowly open the drain valve and fresh water supply to fill. Close the drain when water reaches the shutoff valves.
  8. Close the shutoff valves, then slowly reopen the drain until the gauge reads 45 to 55 psig.
  9. Hold for 10 minutes and confirm the gauge pressure stays constant. Check for leaks and repair any found.
  10. Disconnect the fill hose, drain the boiler through the drain valve, and remove the hose.
  11. Remove the nipples and valves unless they stay in the system piping.
  12. Remove the plug from the relief valve street elbow and install the relief valve per page 9.

Applies to: Ultra Series 4 boilers

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Weil-McLain Series 4 gas-fired water boiler manual, p. 8. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.