Navien · Boiler troubleshooting
Gas supply connection and leak test
What is going on
Gas supply must be connected by a licensed professional using the gas type and pressure on the rating plate. The boiler cannot be converted between natural gas and propane without a Navien gas conversion kit.
Check in this order
- Determine gas type and pressure from the rating plate.
- Perform a pressure test on the main gas supply line.
- Purge the gas line of debris.
- Size the gas line using the tables that follow.
- Install a certified full port valve on the gas supply line and on the boiler.
- Install a manual gas shut-off valve and a sediment trap close to the boiler gas connection.
- Connect the gas supply line; use two wrenches to avoid damaging the boiler connector.
- Leak test all connection points and the boiler using a bubble test, never a flame.
Applies to: NCB700 all models
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: NCB700 Installation & Operation Manual, p. 54. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.