Navien · Boiler troubleshooting

CO2 does not match Table 2 at high fire

NCB-H

What is going on

After orifice and DIP switch setting, CO2 at high fire is outside the target range.

Likely causes

  • Wrong gas orifice installed for the model, gas type or altitude

Check in this order

  1. Do not adjust the gas valve.
  2. Check that the correct orifice is installed per Table 1.
  3. Recheck the DIP switch settings for gas type and altitude.

Applies to: NCB-H boilers during LP conversion

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Navien NCB-H LP gas and high altitude conversion guide, p. 2. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.