Weil-McLain · Boiler troubleshooting
Determine if water treatment is needed and clean the system
What is going on
Petroleum-based cleaning or sealing compounds must not be used in the boiler system. Leaks must be eliminated because continual fresh makeup water shortens boiler life. Sediment must be flushed out before the boiler is connected.
Likely causes
- Sediment in the system affecting chemical treatment or damaging components
- Continual fresh makeup water causing mineral buildup and cast iron overheating
- Water that is very hard (above 7 grains) or low pH (below 7)
Check in this order
- Flush the whole system without the boiler connected until the water runs clean.
- On zoned systems, flush each zone separately through a purge valve; install purge and isolation valves if missing.
- Verify water chemistry; consult a water treatment company for very hard or low-pH water.
- Keep boiler water pH between 7.0 and 8.5.
- Eliminate all system leaks.
Applies to: Water boiler system preparation
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: EG / PEG Series 7 boiler manual, p. 56. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.