Critical setup: boiler model and altitude
What is going on
Boiler model and altitude are critical settings. Wrong values can cause severe injury, death or property damage. Water temperature must also be set correctly for the system, because excessive temperature can damage property. Low-temperature circuits such as radiant slab should be protected by external limit controls wired to the control.
Check in this order
- Confirm the boiler model shown on power-up matches the installed boiler; if not, turn off the boiler and change the setting per page 69.
- Set altitude during the Wizard BOILER SETTINGS step so combustion is correct.
- Set supply temperatures for the actual system.
- Where circuits need lower temperature water, wire an external limit control to the control.
Applies to: SF1000L/R, SF1500L/R, SF2000L/R
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: SlimFit Series 2 Boiler Manual 550-100-561/1225, p. 62. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.