Diagnostics menu run times, counters and lockout history

SlimFit Series 3

What is going on

Read-only history and status items in the DIAGNOSTICS menu. Use them to review past lockouts and operating time.

Check in this order

  1. Review Burner Time, Input 1-3 Time, Network Time and Ignition Count under Run Times.
  2. Review Control Fault, Ignition Retries, Manual Reset Cnt and Auto Reset Cnt under Past Errors.
  3. Open Lockout History 1, 2 or 3 to see Fault Name, Fault Type, Time, Date, Status, Temperatures, Inputs and Outputs at the time of each lockout.
  4. Review Manual Test Mode readings Heat Exchanger, Target, Boiler Out, Boiler In, System Supply, System Return, Flue, Outdoor, Blower Signal, Blower Speed and Flame Signal.

Applies to: SlimFit SF-550 and SF-750 Series 3

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: SlimFit series3 boiler manual, p. 80-81. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.