Connecting Vitodens B2HA with black GUI to the Versatronik 300

Versatronik 300 Cascade Control

What is going on

Same CAT5e daisy-chain method as the HO1 version. The boiler needs its outdoor temperature sensor connected, and the boiler coding addresses differ.

Check in this order

  1. Plug the CAT5e cable into the J1 receptacle at the upper right of the Versatronik 300 PCB.
  2. Daisy-chain the cable from control to control.
  3. Connect the outdoor temperature sensor. If none is available, use a 10 kOhm resistor (brown-black-orange) to simulate about 77F/25C.
  4. Set the boiler coding addresses listed for the B2HA.
  5. Assign each boiler a unique LON address starting at 1 and counting up.

Applies to: Vitodens 200 B2HA with new (black) GUI

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Versatronik 300 Cascade Control V1.4 manual, p. 17. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.