Viessmann · Boiler troubleshooting
Connecting Vitodens B2HA with black GUI to the Versatronik 300
What is going on
Same CAT5e daisy-chain method as the HO1 version. The boiler needs its outdoor temperature sensor connected, and the boiler coding addresses differ.
Check in this order
- Plug the CAT5e cable into the J1 receptacle at the upper right of the Versatronik 300 PCB.
- Daisy-chain the cable from control to control.
- Connect the outdoor temperature sensor. If none is available, use a 10 kOhm resistor (brown-black-orange) to simulate about 77F/25C.
- Set the boiler coding addresses listed for the B2HA.
- Assign each boiler a unique LON address starting at 1 and counting up.
Applies to: Vitodens 200 B2HA with new (black) GUI
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Versatronik 300 Cascade Control V1.4 manual, p. 17. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.