Test fixed high limit (simulation #2, valve closed)
What is going on
Alternate high limit test that uses a closed boiler valve and a jumpered flow switch.
Check in this order
- Close the boiler valve and jumper across the flow switch.
- Run the boiler at high fire. The control should shut it down through the coding card (on B2TB models, set coding address 06 to maximum).
- Keep the boiler temperature rising until the fixed high limit trips.
- After the limit trips, slowly open the boiler valve to cool the boiler down.
Applies to: Vitodens 200-W B2HA 45, 60
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitodens 200-W B2HA 45, 60 Service Instructions, p. 8. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.