Viessmann · Boiler troubleshooting

Extended shut-down and freeze protection

Vitorond 200VD2A

What is going on

Preparation for summer shutdown or freezing conditions.

Check in this order

  1. After the heating season, clean the combustion chamber, flue gas passages and, as needed, the vent connector to prevent corrosion.
  2. Keep the boiler and system filled with water; do not drain unless freezing is possible.
  3. If freezing is possible without antifreeze, drain the boiler and system.
  4. Close the valve before the automatic feed valve, and leave other valves, air vents and drain valves open.
  5. Reprogram the control after a long power interruption if the control requires it.

Applies to: Vitorond 200 VD2A boilers

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitorond 200 VD2A installation manual, p. 36. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.