Combustion and ventilation air supply
What is going on
The boiler room needs adequate fresh combustion and ventilation air. Negative pressure and blocked air openings can cause flue gases to enter the living space.
Likely causes
- Negative pressure from exhaust, attic or dryer fans
- Covered boiler or combustion air opening
- Chemicals, aggressive vapors or high dust in the room
Check in this order
- Make combustion and ventilation air provisions per local codes. Without local codes use CAN/CSA-B149.1 or .2 in Canada, or section 5.3 of ANSI Z223.1 in the US. For oil use CSA B-139 or NFPA 31.
- Install the boiler near an outside wall where possible so fresh air can be ducted directly to it.
- Make sure the boiler room is never under negative pressure.
- Never cover the boiler, store debris near it, or block the combustion air opening or the draft hood.
- Do not install the boiler where chemicals, aggressive vapors, high dust or high humidity are present.
Applies to: VD2-320 to VD2-1080
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitorond 200 VD2 installation manual, p. 35. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.