Weil-McLain · Boiler troubleshooting
Check the water system and automatic air vents
What is going on
Annual check of fill pressure, pressure rise and air vents.
Likely causes
- Leaking automatic air vents
- Pressure rising too high on heat-up, pointing to expansion tank problems
Check in this order
- Verify all system components are installed correctly and working
- Check cold fill pressure and verify it meets the minimum water pressure in Table 5, p. 21
- Watch system pressure as the boiler heats up; excessive rise points to an expansion tank problem
- Remove air vent caps and briefly press the push valve to flush each vent; reinstall the caps
- Confirm vents do not leak; replace any leaking vent
- Check system water chemistry (see p. 92)
Applies to: SVF 500/600 Series 1 boiler
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: SVF 500/600 Series 1 boiler manual, p. 107. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.