Weil-McLain · Boiler troubleshooting

Check the water system and automatic air vents

SVF 500/600 Series 1

What is going on

Annual check of fill pressure, pressure rise and air vents.

Likely causes

  • Leaking automatic air vents
  • Pressure rising too high on heat-up, pointing to expansion tank problems

Check in this order

  1. Verify all system components are installed correctly and working
  2. Check cold fill pressure and verify it meets the minimum water pressure in Table 5, p. 21
  3. Watch system pressure as the boiler heats up; excessive rise points to an expansion tank problem
  4. Remove air vent caps and briefly press the push valve to flush each vent; reinstall the caps
  5. Confirm vents do not leak; replace any leaking vent
  6. Check system water chemistry (see p. 92)

Applies to: SVF 500/600 Series 1 boiler

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: SVF 500/600 Series 1 boiler manual, p. 107. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.