Cleaning the burners (fan, venturi and burner tube)
What is going on
Clean the burner fan and burner tube. Close the central gas shut-off valve before any work.
Check in this order
- Close the central gas shut-off valve.
- Disconnect the venturi mixing tube from the fan.
- Detach the venturi mixing tube with the combination gas valve and gas connector pipe. Detach connector pipes if fitted.
- Detach the connector from the fan and dismantle the fan.
- Clean the fan housing and fan impeller with compressed air.
- Vacuum the burner tube from inside and out if needed.
- Reassemble in reverse order. Make sure the gasket between fan housing and burner plate is positioned correctly; replace it if damaged.
- Check for gas leakage at the screws and at the gasket between fan housing and burner plate.
Applies to: Vitocrossal 300 CA3B Series 2.5 to 6.0
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Viessmann Vitocrossal 300 CA3B service instructions, p. 73. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.