Cleaning the burners (fan, venturi and burner tube)

Vitocrossal 300 CA3B

What is going on

Clean the burner fan and burner tube. Close the central gas shut-off valve before any work.

Check in this order

  1. Close the central gas shut-off valve.
  2. Disconnect the venturi mixing tube from the fan.
  3. Detach the venturi mixing tube with the combination gas valve and gas connector pipe. Detach connector pipes if fitted.
  4. Detach the connector from the fan and dismantle the fan.
  5. Clean the fan housing and fan impeller with compressed air.
  6. Vacuum the burner tube from inside and out if needed.
  7. Reassemble in reverse order. Make sure the gasket between fan housing and burner plate is positioned correctly; replace it if damaged.
  8. Check for gas leakage at the screws and at the gasket between fan housing and burner plate.

Applies to: Vitocrossal 300 CA3B Series 2.5 to 6.0

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Viessmann Vitocrossal 300 CA3B service instructions, p. 73. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.