Wiring zone valves with 24 VAC powered thermostats
What is going on
Same zone valve layout, with thermostats powered by 24 VAC. The boiler's internal 24 V transformer (75 VA) powers the zone valves, LWCO switches and thermostat terminals.
Check in this order
- Connect zone valves 1 to 3 with NO/NC/COM as in the zone valve layout.
- Connect each thermostat to its 24 VAC line and neutral terminals.
- Check the total zone valve load does not exceed 72 VA; otherwise add an external zone valve controller.
Applies to: NCB700 boilers with zone valves
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Navien NCB700 installation and operation manual, p. 214. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.