Rinnai · Boiler troubleshooting

Room air multiple boiler vertical termination

I-Series Plus

What is going on

Exhaust termination spacing for room air installations with multiple boilers.

Check in this order

  1. Use only listed Category IV venting for room air installations.
  2. Place all terminations (horizontal and/or vertical) at least 12 in above grade or anticipated snow level.
  3. Keep 12 in (0.30 m) minimum clearance from the roof to the termination.
  4. Keep 60 in (1.52 m) vertical spacing between terminals.
  5. Keep 12 in (0.30 m) clearance from the inside corner.

Applies to: Room air venting with multiple boilers

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Rinnai I-Series Plus IP060160C installation and operation manual, p. 40. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.