Room air multiple boiler vertical termination
What is going on
Exhaust termination spacing for room air installations with multiple boilers.
Check in this order
- Use only listed Category IV venting for room air installations.
- Place all terminations (horizontal and/or vertical) at least 12 in above grade or anticipated snow level.
- Keep 12 in (0.30 m) minimum clearance from the roof to the termination.
- Keep 60 in (1.52 m) vertical spacing between terminals.
- Keep 12 in (0.30 m) clearance from the inside corner.
Applies to: Room air venting with multiple boilers
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Rinnai I-Series Plus IP060160C installation and operation manual, p. 40. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.