Viessmann · Boiler troubleshooting
Mounting boiler on wall bracket
What is going on
Hang the boiler on the levelled wall bracket and level it before connecting piping.
Check in this order
- Confirm the bracket is fastened tightly and is level; a loose bracket is a severe safety hazard.
- Remove the external accessories connection box cover.
- Loosen the screws at the bottom of the boiler; do not remove them completely.
- Lift the front enclosure panel up and pull it away from the boiler.
- Mount the boiler onto the bracket.
- Adjust the levelling screws until the boiler is level, checking with the round bubble level on top.
- Install the supplied installation fittings per the layout on p. 11.
- Make sure the boiler is level vertically and horizontally so the condensate drains properly.
Applies to: Vitodens 200-W B2HB 45, 57, 160, 199
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitodens 200-W B2HB 45, 57, 160, 199 Installation Instructions, p. 13, p. 15. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.