Check burner refractory, cylinder burner and flue gas flapper
What is going on
Inspection and replacement of the burner refractory, cylinder burner assembly and flue gas flapper.
Check in this order
- Check the burner refractory ring C and cylinder burner E for damage. Replace if needed.
- Remove electrode block and ionization electrode A.
- Undo the three clips B and remove refractory ring C.
- Loosen the four Torx screws D and remove cylinder burner E and assembly gasket F.
- Fit new cylinder burner and new gasket. Tighten to 3.3 lb.ft (4.5 Nm) with a calibrated torque wrench.
- Reinstall refractory ring C and secure with clips B.
- Reinstall electrode block and ionization electrode A. Tighten to 2.6 lb.ft (3.5 Nm).
- To check the flue gas flapper, remove fan A (three screws), remove flapper B and check flapper and gasket for dirt and damage. Replace if needed.
- Refit flapper B and refit fan A with three screws to 2.2 lb.ft (3.0 Nm).
Applies to: Vitodens 200-W B2HB 45, 57, 160, 199
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitodens 200-W B2HB 45, 57, 160, 199 Service Instructions, p. 24. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.