Weil-McLain · Boiler troubleshooting

Radiant heating zoning, primary/secondary

SVF 500/600 Series 1

What is going on

The SVF is suited to radiant heating and can operate in condensing mode. Boiler return water temperature does not need regulating in radiant applications. The primary/secondary piping keeps the boiler loop supplied with sufficient flow and keeps the boiler circulator's high head off the zone valves.

Check in this order

  1. Size the system piping and circulators for the flow and pressure drop needed.
  2. Build the primary/secondary connection with tees no more than eight pipe diameters apart.
  3. Install the flow/check valve on the boiler outlet to prevent gravity circulation during DHW heating.
  4. Install an optional high limit temperature control, set to protect the radiant system, if required (Figure 18).
  5. Install a bypass pressure regulator where high-head pumps require one.

Applies to: SVF 500/600 boilers feeding radiant heating loops

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: SVF 500/600 Series 1 Boiler Manual, p. 26. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.