What is going on
The SVF is suited to radiant heating and can operate in condensing mode. Boiler return water temperature does not need regulating in radiant applications. The primary/secondary piping keeps the boiler loop supplied with sufficient flow and keeps the boiler circulator's high head off the zone valves.
Check in this order
- Size the system piping and circulators for the flow and pressure drop needed.
- Build the primary/secondary connection with tees no more than eight pipe diameters apart.
- Install the flow/check valve on the boiler outlet to prevent gravity circulation during DHW heating.
- Install an optional high limit temperature control, set to protect the radiant system, if required (Figure 18).
- Install a bypass pressure regulator where high-head pumps require one.
Applies to: SVF 500/600 boilers feeding radiant heating loops
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: SVF 500/600 Series 1 Boiler Manual, p. 26. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.