Viessmann · Boiler troubleshooting

Burner does not switch off at the correct time

Versatronik 200

What is going on

Burner keeps running past the programmed heating time.

Likely causes

  • Operating mode or heating program does not match the schedule.
  • Minimum boiler temperature setting holds the burner on.

Check in this order

  1. Check the operating mode is Standard F (test B).
  2. Check the time and heating program (heating time).
  3. Check the pump switching mode as for pumps that do not switch off.
  4. Check the minimum boiler temperature and the type of minimum limiter (corrosion protection).

Applies to: Versatronik 200 heat generator control

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Versatronik 200 installation and operating manual, p. 167. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.