Weil-McLain · Boiler troubleshooting

SVF header (system) sensor failed

SVF Series 1SVF Series 2

What is going on

The outdoor sensor and header/system supply sensor connect to the master boiler. If the header sensor fails, the control falls back to the boiler's own outlet temperature, or another boiler's header sensor if one is connected. The system keeps heating but control is less accurate.

Likely causes

  • Header sensor open or shorted
  • Sensor wiring damaged or loose
  • Sensor not the 12k ohm type

Check in this order

  1. Power off before working on sensor wiring.
  2. Check the header sensor connections at the master boiler.
  3. Check the sensor is a 12k thermistor and measure it against its temperature chart.
  4. Replace the sensor or fix the wiring, then check the master reads header temperature again.

Applies to: SVF 725, 850, 1000 (Series 1) and SVF 1500-3000 (Series 2)

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Weil-McLain SVF 725/850, 1000 Series 1 / 1500-3000 Series 2 Advanced Installation Manual 550-143-071/0924, Express Setup steps (sensors) p.12; control features p.10. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.