Weil-McLain · Boiler troubleshooting
Monthly automatic air vent check
What is going on
Confirm each automatic air vent in the system vents freely and does not leak.
Likely causes
- Air vent valve stuck or leaking
- Vent cap left too tight to allow venting
Check in this order
- Remove the cap from the automatic air vent.
- Depress valve B slightly with a screwdriver tip to check operation.
- If the valve moves freely and does not leak, replace cap A, turning it all the way on.
- Loosen cap A one turn so the vent can operate.
- Have the vent replaced if it does not operate correctly.
Applies to: Automatic air vents on the heating system (if used)
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Ultra Series 4 user's information manual, p. 7. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.