Weil-McLain · Boiler troubleshooting
Gas leak check and inlet pressure check
What is going on
Confirm gas supply pressure at the gas valve test port and check for leaks safely.
Check in this order
- Purge all air from the gas supply piping.
- Check the boiler and its gas connection for leaks before starting the boiler. Use a soapy water bubble test only. Never use an open flame.
- For pressure tests below 14 in W.C., close the manual main shut-off valve.
- For pressure tests above 14 in W.C., disconnect the boiler gas connection from the supply piping.
- Connect a manometer or pressure gauge to the tapping on the gas line elbow by the gas valve (Figure 54, p. 63).
- With all gas appliances running, verify minimum pressure at high fire during startup: at least 3.5 in W.C. with gas flowing.
- Confirm the maximum supply pressure is 14 in W.C., whether the boiler is running or off. Install a lock-up regulator if needed (p. 62).
Applies to: SVF 500/600 gas supply and gas valve test port
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Weil-McLain SVF 500/600 Series 1 boiler manual, p. 63. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.