Viessmann · Boiler troubleshooting

Connecting combustion air device (blower and proving switch)

Vitotronic 100 GC1

What is going on

Wiring a 120 VAC combustion air blower through the Combustion Air Device Adaptor, with a proving switch.

Check in this order

  1. Disconnect power to the control and burners.
  2. Install the Combustion Air Device Adaptor (PN 7134 563) on the DIN rail inside the connection enclosure, per the adaptor manual.
  3. Remove the jumper between terminals 16 and 17.
  4. Connect wire BK2 to terminal 16 and BK3 to terminal 17. Do NOT reverse them.
  5. Connect the blower to the adaptor as shown: 120 VAC, max 5 FLA, recommended wire AWG 14. Confirm the blower suits the application.
  6. Wire the proving switch as normally open, rated 120 VAC.
  7. Provide disconnect means and overcurrent protection as required by local codes.

Applies to: Vitotronic 100 GC1 combustion air blower and proving switch

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotronic 100 GC1 / 300-K MW1S installation and service instructions, p. 40. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.