Weil-McLain · Boiler troubleshooting

Install low water cut-off (LWCO)

ECO Tec Series 3

What is going on

LWCO is required and is installer supplied. Use the Weil-McLain LWCO kit where possible.

Check in this order

  1. Install the low water cut-off per Figure 55, page 47.
  2. If using the Weil-McLain LWCO kit, connect its harness to J21 as shown in the control wiring diagram.
  3. If using another LWCO, it must have an isolated contact. Clip the factory jumper and connect the device to J21 as shown in the wiring diagram.
  4. Route the LWCO harness from its mounting location to the control. Provide strain relief and a seal at the cabinet entry if mounted outside the cabinet.

Applies to: ECO Tec Series 3 all models

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: ECO Tec series 3 condensing gas boiler boiler manual, p. 71. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.