Viessmann · Boiler troubleshooting

Check the boiler and DHW tank temperature sensors

Vitotronic 300 GW2

What is going on

Compare the sensor resistance against the temperature. Replace the sensor if the value differs significantly.

Check in this order

  1. Disconnect plug in the terminal compartment.
  2. Measure resistance at terminals 1 and 2 of the plug (or 2 and 3 if a second DHW tank sensor is connected).
  3. Compare with the table 40 °C / 104 °F about 578, 50 °C / 122 °F about 597, 60 °C / 140 °F about 616.
  4. If the value differs significantly, check installation and replace the sensor if needed.

Applies to: Boiler temperature sensor 7450 632 and DHW tank temperature sensor 7450 633

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotronic 300 GW2 installation and service instructions, p. 101. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.