External heating program changeover
What is going on
A dry contact changes the heating program. At plug avD, coding 91 (General group) assigns the function to the heating circuits. With extension EA1, set 5D, 5E or 5F to 1, and use coding D8 in the heating circuit group. The changeover can be set separately for heating circuits 1 to 3.
Check in this order
- Use a potential-free dry contact.
- At plug avD, set coding 91 (General group) to assign the function to the heating circuits.
- With extension EA1, set 5D, 5E or 5F (General group) to 1.
- Set coding D8 in the heating circuit group if using EA1.
- Set changeover separately for heating circuits 1 to 3 as needed.
Applies to: Heating program changeover
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitotronic 200 and 300-K Installation and Service, p. 22. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.