Viessmann · Boiler troubleshooting

Set DHW recirculation pump cycles for individual weekdays

Vitotrol 300

What is going on

Use this procedure to give each weekday its own recirculation pump cycles.

Check in this order

  1. Open the flip-down cover of the remote control.
  2. Select 'Time Program DHW Recirculation Pump' and wait for the display.
  3. Select 'Individual?' and confirm.
  4. Use the up/down keys to choose the weekday.
  5. Select 'DHW Recirculation Pump Cycle 1', then 'Cycle 1 On'.
  6. Enter the start time and confirm, then enter the end time and confirm.
  7. Set cycles 2 to 4 the same way.
  8. Close the flip-down cover.
  9. To view the cycles, press the two overview keys together. The selected cycles appear on a time line.

Applies to: Vitotrol 300 remote control, DHW recirculation pump

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotrol 300 operating instructions, p. 19. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.