Burner motor power supply, 240 VAC 1 PH

Vitotronic 300

What is going on

For burners with 240 VAC single-phase supply and conduit connection. Fuse and wire sizing come from the burner manual.

Check in this order

  1. Disconnect power to the burner and the boiler control.
  2. Connect 240 VAC to terminals 21, 22 and 23 on the DIN rail in the connection enclosure.
  3. Provide a fuseable disconnect according to local codes.
  4. Connect the supplied power cable to the motor terminals on the burner.
  5. Connect the cable plug to the socket on the DIN rail in the connection enclosure.

Applies to: VD2/VD2A/CT3 controls, 240 VAC 1 PH burners

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotronic 300 GW2 installation and service instructions, p. 53. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.