Fixed high limit test, simulation #1 (flue gas test with boiler pump unplugged)
What is going on
Test of the fixed high limit (manual reset) using the flue gas test mode. Pump plug disconnected to let temperature rise. Observe the temperature and make sure the limit trips.
Check in this order
- Make sure the boiler and boiler pump are in normal operating condition.
- Remove the cover at the back of the boiler control to reach the control plugs.
- In the extended menu of the operating manual, select 'Test mode', then 'flue gas test ON', and press OK.
- Wait for the burner to ignite and go to high fire.
- Once the burner is lit, carefully unplug the boiler pump plug sÖ from the control board.
- Watch the boiler temperature on the display. The burner will shut off, then the temperature should keep rising.
- At 210°F (99°C) the manual reset high limit should trip and give an F2 fault.
- If the limit is not reached, repeat with one extra step: two minutes after burner shut-off, plug the pump back in for no more than 1 second.
Applies to: Vitodens 200-W B2HA 45, 60 (CSD-1 high limit field test)
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitodens 200-W B2HA 45, 60 installation instructions, p. 7. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.