Check combi DHW function, 3-way valve and brazed plate
What is going on
Verify the combi boiler switches between space heat and domestic hot water.
Likely causes
- 3-way valve not switching
- Leak at valve or brazed plate fittings
- Clogged DHW filter
Check in this order
- Give a heat call, then open a faucet to start a DHW call.
- Confirm the boiler and valve switch from space heating to DHW and hot water is delivered.
- If needed, run the 3-way valve test on p. 143.
- Check for water leaks at the 3-way valve, brazed plate and brazed plate manifold fittings.
- Clean the DHW brazed plate annually (p. 154).
- Clean the domestic inlet external filter and the combi manifold DHW flow switch and bypass filters (p. 157).
- Check DHW temperatures at all fixtures per the mixing valve procedure (p. 137). Check the recirculation pump, aquastat, timer or occupancy sensor if used.
Applies to: Combi models only
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: ECO Tec series 3 boiler manual, p. 144. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.