Weil-McLain · Boiler troubleshooting

Check combi DHW function, 3-way valve and brazed plate

ECO Tec Series 3

What is going on

Verify the combi boiler switches between space heat and domestic hot water.

Likely causes

  • 3-way valve not switching
  • Leak at valve or brazed plate fittings
  • Clogged DHW filter

Check in this order

  1. Give a heat call, then open a faucet to start a DHW call.
  2. Confirm the boiler and valve switch from space heating to DHW and hot water is delivered.
  3. If needed, run the 3-way valve test on p. 143.
  4. Check for water leaks at the 3-way valve, brazed plate and brazed plate manifold fittings.
  5. Clean the DHW brazed plate annually (p. 154).
  6. Clean the domestic inlet external filter and the combi manifold DHW flow switch and bypass filters (p. 157).
  7. Check DHW temperatures at all fixtures per the mixing valve procedure (p. 137). Check the recirculation pump, aquastat, timer or occupancy sensor if used.

Applies to: Combi models only

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: ECO Tec series 3 boiler manual, p. 144. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.