Viessmann · Boiler troubleshooting

Combustion air device connection (VD2/VD2A/CT3)

Vitotronic 100 GC1

What is going on

Connect a combustion air blower through the combustion air device adaptor.

Check in this order

  1. Disconnect power to the control and burners.
  2. Mount the combustion air device adaptor (part no. 7134 563) on the DIN rail inside the connection enclosure, following the adaptor's manual.
  3. Remove the jumper between terminals 16 and 17.
  4. Connect wire BK2 to terminal 16 and BK3 to terminal 17. Do not reverse them.
  5. Wire the blower to the adaptor as shown in the diagram.

Applies to: VD2, VD2A and CT3 combustion air blower

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Viessmann Vitotronic 100 GC1 / Vitocontrol-S VD2/CT3/CM2 installation and service instructions, p. 54. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.